Logo
 
Menu
 
 
 

Hykon STATCOM is available in the following Series according to their function:

• Hykon STATCOM H Series – Harmonic Filtering

• Hykon STATCOM P Series – Reactive Power Factor Correction

• Hykon STATCOM HP Series – Harmonic & Reactive Power Factor Correction

Click here to Download Brochure >>

Hykon STATCOM H Series is a Harmonic filter.

Functions:

• The Hykon STATCOM H continuously monitors the harmonic current demanded by the load and generates an adaptive waveform which matches   exactly the shape of the non linear portion of the load current.

• Hykon STATCOM H injects this adaptive current into the load at the point of connection. Only fundamental (50Hz) current is drawn from the source   by the load.

• Compensates from the 2nd to the 13th harmonic in a response time of less than 100 micro-seconds.

Features

• IGBT Based PWM Voltage Source Converter technology.

• Noval control for harmonic filtering.

• Simultaneous filtering upto 13th Harmonics.

• Harmonic current filtering in compliances with IEEE standards.

• Excellent dynamics with response time less than 1 millisecond.

  Go to Top
 

Hykon STATCOM P Series is a Shunt Active Power Factor Controller.

Functions:

• Hykon STATCOM P continuously monitors the Power Factor of the connected non linear load and corrects the phase angle of the current wave   form by switching the IGBT based inverter.

Features

• IGBT Based PWM Voltage Source Converter technology.

• Maintain Grid Power Factor near to Unity for non-linear loads.

• Reduce Maximum Demand.

• Excellent Dynamics with response time less than 1 millisecond.

  Go to Top
 

Hykon STATCOM HP- Series is a Harmonic Filter as well as an Active Power Factor Conditioner.


Functions:

• The Hykon STATCOM HP continuously monitors the harmonic current demanded by the load and generates an adaptive waveform which matches    exactly the shape of the non linear portion of the load current.

• Hykon STATCOM HP injects this adaptive current into the load at the point of connection. Only fundamental (50Hz) current is drawn from the source    by the load.

• Compensates from the 2nd to the 51st harmonic in a response time of less than 100 micro-seconds.

• Hykon STATCOM HP continuously monitors the Power Factor of the connected non linear load and corrects the phase angle of the current wave    form by switching the IGBT based inverter.

Features

• IGBT Based PWM Voltage Source Converter technology.

• Noval control for harmonic filtering.

• Simultaneous filtering upto 13th Harmonics.

• Reduce Maximum Demand.

• Harmonic current filtering in compliances with IEEE standards.

• Maintain Grid Power Factor near to Unity for non-linear loads.

• Excellent Dynamics with response time less than 1 millisecond.

  Go to Top
 
1 Models STATCOM H STATCOM P STATCOM HP
2  Capacity
10 KVA to 250 KVA Scalable
3  Input Parameters
 Input Voltage
415V 3-Phase, 4 Wire
 Frequency
50 ± 3 Hz
4  Functions
Grid Power factor correction
Nil
Yes : 0.98 - 1
Yes : 0.98 - 1
Harmonic filtering: IEEE Std
Yes : <5%
No
Yes : <5%
Transient current suppression
Yes
 Rapid Load Variation
Yes
 Parallel Configuration
Yes
 Response Time
100 micro-seconds 
5  Control Strategy
100 micro-seconds 
DSP based control card
Using D-Q Theory
6  DC Parameters - Inverter
 DC Bus Voltage
700V ± 2%
 DC Bus Over Load Trip
750V
7  Power Circuit
 Power Device
IPM – IGBT Module
8  Configuration
IGBT Inverter – 1 x 3 phase bridge for Shunt
9  Cooling
Forced air
10  Front Panel Indications  Input voltage : LCD
 Reset Switch
 Power ON/OFF Switches
 Fault : LED
11  Environmental Conditions
 Operating Temperature
0 to 40°C continuous
 Storage Temperature
-30°C to +65°C
 Relative Humidity
up to 95%, non-condensing
 Operating Altitude
up to 1500 m
 